ANTI-ISLANDING RELAY UFR1001E

MONITORS VOLTAGE AND FREQUENCY IN PLANTS FOR OWN GENERATION OF ELECTRICITY


Brand: Victron

Reference No. REL100100000

0

742.00 Incl

674.55 Excl
Add to Cart

The UFR1001E monitors voltage and frequency in plants for own generation of electricity. It fulfills the requirements of VDE-AR-N 4105 bdew-directive, G59/3, G83/2 and ÖVE/ÖNORM E 8001-4-712:2009 for generators connected to the public grid. 

Power Supply

Rated supply voltage Us

 

AC/DC 24-270 V, 0/45...65 Hz, <5VA DC: 20,4...297 V, AC: 20,4...297 V

 

Relay output

 

 

2 change-over contacts

type 2, see "general technical informations"

 

Voltage

 

Measurement voltage phase- phase

Setting range phase-phase

Measuring voltage phase-neutral

Setting range phase-neutral

Measurement method Hysteresis

Measurement accuracy (with neutral)

Measurement accuracy (without neutral)

Accuracy of display

 

Measurement functions Switching-delay (dAL) Switching-back-delay (doF)

AC 15...530 V (< 5 V display: 0)

 

AC 15...520 V

 

AC 10...310 V (< 5 V display: 0)

 

2

 
AC 15...300 V

 

true RMS adjustable1,0...99,9 V

±0,6% of measured value

 

±0,8% of measured value

 

>100V: -1 digit (resolution 1 V)

<100V: -1 digit (resolution 0,1 V) 3-phase with / without neutral adjustable 0,05(±15ms)...130,0 s

adjustable 0 (approx. 200 ms)...1000 s

 

Frequency

 

Measurement range Setting range Hysteresis Measurement accuracy

Switching delay (dAL)

Switching-back-delay (doF)

 

40...70 Hz

45,00...65,00 Hz

0,05...10,00 Hz

± 0,04 Hz ± 1 digit

 

adjustable 0,05(±15ms)...130,0 s

 

adjustable 0 (>200 ms)...999 s

 

Vector-Shift

 

Measurement range

Setting range Switching-delay (dAL)

Switching-back-delay (doF)

Delay at Us on

 

0...45,0°

 

2,0...20,0°

< 50 ms

 

adjustable 3...240 s

 

adjustable 2...20 s

 

ROCOF (df/dt)

 

Setting range

 

0,100...5,000 Hz/s, 4...50 cycles

 

Digital outputs insulated

 

Voltage I1 Current Q1...Q5

 

DC 4,5...27 V

max. 20 mA / output

 

 

Input Feed-back-contacts

 

Voltage Y0...Y1/2

Switching time connected switches

 

DC 15...35 V

adjustable 0,5...99,0 s

 

 

Test Conditions

 

 

Rated impulse voltage

Overvoltage category

Rated Insulation voltage Contamination level Isolation material group

ON-period

Rated ambient temp. range

 Interference resistance Interference transmission

 

EN 60255

4000 V

 

III

 

2

 

300 V

II

 

100 %

-20 °C...+55 °C EN 60 068-2-2 dry heat

 

EN 61 000-6-2

 

EN 61 000-6-4

 

Housing

 

Design

Dimensions (h x w x d)

Protection housing Protectionterminals Attachment

 

Weight

 

V6

90 x 105 x 69 mm, mounting height 66 mm

IP30

IP20

DIN-rail 35 mm according to EN 60 715 or screws M4

ca. 250 g

 

Spec Sheet-